維修包米勒伺服驅動器:705:Motor temperature for characteristic curve of ASM slip invalid, lower than -50°C or higher than 200°C。ASM滑動特性曲線的電機溫度無效,低于-50°C或高于200°C
宜興鮑米勒伺服驅動器維修技巧:The motor temperature that is measured via the KTY encoder is monitored for asynchronous motors due to slip characteristic curves
If the temperature is lower than -50°C or higher than 200°C, the temperature values are assumed to be invalid and the error will be triggered.通過KTY編碼器測量的電機溫度因滑動特性曲線而對異步電機進行監測如果溫度低于-50°C或高于200°C,則假定溫度值無效,并將觸發錯誤。
Cause:
The KTY motor temperature encoder was incorrectly connected or not at all connected. KTY電機溫度編碼器連接不正確或根本沒有連接。
Remedy through: 補救措施:Check connections and cable of KTY motor temperature encoder.檢查KTY電機溫度的連接和電纜編碼器。
Monitoring may be deactivated for intended operation without temperature encoder.在沒有溫度編碼器的情況下,可針對預期操作停用監控。
Cause: 原因:
KTY motor temperature encoder defective. KTY電機溫度編碼器故障。
Remedy through: A defective KTY motor temperature encoder generally requires
motor replacement.有缺陷的KTY電機溫度編碼器通常需要電機更換。
Monitoring may be deactivated for intended operation without temperature encoder.
在沒有溫度編碼器的情況下,可針對預期操作停用監控。
Cause:原因:
Evaluation switch of the KTY motor temperature encoder in the drive controller is defective. 驅動控制器中KTY電機溫度編碼器的評估開關存在故障。
Remedy through: Drive controller replacement.更換驅動器控制器。
Monitoring may be deactivated for intended operation without temperature encoder.
在沒有溫度編碼器的情況下,可針對預期操作停用監控。
維修包米勒伺服驅動器 BUM62T-100-130--M-024 *維修BUM60, BUM61, BUM62, BUM63, BUM, BKH63, BUS621, BUS622, BUS623, BUS624, BUG622, BUG623, BUM616, BUM617, BUM618, BUM619, BUG3, BUG2, BUG20, BUS3, BUS2, BUS20, BUS6V, BMAXX 4400, BMAXX 4500
轉載請注明出處:上海仰光電子科技專業伺服驅動器維修,伺服電機維修
本文鏈接:http://m.edulz.com.cn/fuwu/Services_Show21195.htm
伺服驅動器維修 伺服電機維修 觸摸屏維修 變頻器維修
電話:021-50157782
手機:13817011982 微信同號
郵箱:shygdzi@163.com
聯系人:張工
網址:http://m.edulz.com.cn
【 我們確保修好測試好給客戶!!!!】
下一篇:東曹凝膠滲透色譜儀HLC-8321GPC常見故障維修方法